Noise
Cooling equipment, fans and backup generators produce both ordinary noise and low-frequency sound. Standard decibel readings capture the first well and the second poorly.
The facts
Every 10 dB sounds about twice as loud. Decibel readings do not capture low-frequency hum well.
Government Virginia JLARC, Dec 2024 · Government CDC / NIOSH · News Technical.ly (Kent County)
Sources update: rarely — one-time study (2024); limits change only when amended · We check for new editions monthly
| Sound or limit | Level | Where or how measured | Source |
|---|---|---|---|
| Everyday sounds | |||
| Refrigerator humming | 40 dB | Typical level | GovernmentNIDCD (NIH) common sounds |
| Normal conversation | 50–65 dB | Typical level | GovernmentNIDCD (NIH) common sounds |
| Vacuum cleaner | 70 dB | Typical level | GovernmentNIDCD (NIH) common sounds |
| Average city traffic | 80 dB | Typical level | GovernmentNIDCD (NIH) common sounds |
| Lawn mower | 85 dB | Typical level | GovernmentNIDCD (NIH) common sounds |
| Jet flyover | 103 dB | 1,000 ft away | GovernmentNIDCD (NIH) common sounds |
| Data centers and equipment | |||
| Data center noise at Virginia sites that drew complaints | 40–59 dBA | Estimated, at nearby homes | GovernmentVirginia JLARC, 2024, pp. 76–78 |
| Large backup generator (2 MW) in a sound-reducing enclosure | 74–79 dBA | 23 ft away; two enclosure options | IndustryCaterpillar, 2024 |
| Construction-site generator | 81 dBA | 50 ft away, measured maximum | GovernmentFHWA construction noise model, Table 1 |
| Jackhammer | 89 dBA | 50 ft away, measured maximum | GovernmentFHWA construction noise model, Table 1 |
| Impact pile driver | 101 dBA | 50 ft away, measured maximum | GovernmentFHWA construction noise model, Table 1 |
| Limits and guidelines | |||
| EPA level to protect health and welfare outdoors in residential areas | 55 dB | Day–night average (Ldn); a guideline, not a rule | GovernmentEPA “Levels Document,” 1974, Table 1 |
| Kent County, Del. data center limit | 55 dBA | At the site’s property line, all equipment combined | GovernmentKent County Ordinance LC26-06, §205-72.H |
| Fairfax County, Va. residential noise limit | 60 dBA day · 55 night | At the property line | GovernmentFairfax County Code §108.1-4-2 |
| Homes compatible with airport noise below | 65 dB | Day–night average (DNL) | GovernmentFAA, 14 CFR 150, App. A · HUD, 24 CFR 51.103 |
| Federal highway noise level that triggers a review for homes | 67 dBA | Hourly average outdoors | GovernmentFHWA, 23 CFR 772, Table 1 |
| Recommended 8-hour workplace limit | 85 dBA | Average over a work shift | GovernmentCDC / NIOSH |
| Legal 8-hour workplace limit | 90 dBA | Average over a work shift | GovernmentOSHA, 29 CFR 1910.95 |
Reading the table: distance matters. From a single source, sound drops about 6 dB each time the distance doubles, so a generator at 23 ft is much quieter at a home several hundred feet away (FHWA noise fundamentals). “dBA” weights sound the way the ear hears ordinary noise; it under-counts low-frequency hum. Averages over a day or an hour are not the same as a level at one moment. The everyday-sound levels come from a 1990 government table (archived copy). Data center rows are shaded.
Still uncertain: few local codes measure low-frequency sound; JLARC suggests adding C-weighted limits, which capture it better.
Government Kent County limit: Kent County Ordinance LC26-06, §205-72.H (text as introduced, June 2026) · News Technical.ly, Jul 2026 (adoption).
Opinion · Paired with an opposing view
Opinion: opposing views on noise
Loading…